Every member from our high efficiency sales team values customers' needs and business communication for Water Temperature Sensor, Rain Gauge For Soil Moisture, Total Air Temperature Sensor, All prices depend upon the quantity of your order; the more you order, the more economical the price is. We also offer good OEM service to many famous brands.
Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng Detail:

● Sensor Type: Catalytic sensor
● Detect gas: CH4/Natural gas/H2/ethyl alcohol
● Measure range: 0-100%lel or 0-10000ppm
● Alarm point: 25%lel or 2000ppm ,adjustable
● Accuracy: ≤5%F.S
● Alarm: Voice + vibration
● Language: Support English& Chinese menu switch
● Display: LCD digital display, Shell Material: ABS
● Working voltage: 3.7V
● Battery capacity: 2500mAh Lithium battery
● Charging voltage: DC5V
● Charging time: 3-5hours
● Ambient environment: -10~50℃,10~95%RH
● Product Size: 175*64mm( not including the probe)
● Weight: 235g
● Packing: Aluminum case
The dimension diagram is shown in Figure 1:

Figure 1 Dimension diagram

Figure 1 Dimension diagram

Product lists shown as table 1.
Table 1 Product list

Item No.

Name

1

Portable combustible gas leak detector

2

Instruction manual

3

Charger

4

Qualification Card

Detector Instruction
The specification of instrument parts is shown in Figure 2 and table 2.

Table 2 Specification of instrument parts

No.

Name

Figure 2 Specification of instrument parts

Figure 2 Specification of instrument parts

1

Display Screen

2

Indicator light

3

USB charging port

4

Up key

5

Power button

6

Down Key

7

Hose

8

Sensor

3.2 Power on
Key description is shown in table 3
Table 3 Key Function

Button

Function description

Note

Up, value +, and screen indicating function  
starting Long press 3s to boot up
Press to enter the menu
Short press to confirm operation
Long press 8s to restart the instrument
 

Scroll down, left and right switch flicker, screen indicating function  

● Long pressstarting 3s to start up
● Plug in the charger and the instrument will start automatically.
There are two different ranges of the instrument. The following is an example of a range of 0-100% LEL.

After starting up, the instrument displays the initialization interface, and after initialization, the main detection interface is displayed, as shown in figure 3.

Figure 3 Main Interface

Figure 3 Main Interface

The instrument testing near the location of the need to detect, the instrument will show detected density, when the density exceeds bid, instrument will sound alarm, and accompanied by vibration, the screen above the alarm icon0p appears, as shown in figure 4, the lights changed from green to orange or red, orange for first alarm, red for the secondary alarm.

Figure 4 Main interfaces during alarm

Figure 4 Main interfaces during alarm

Press ▲ key can eliminate alarm sound, alarm icon change to2d. When the instrument concentration is lower than the alarm value, the vibration and alarm sound stop and the indicator light turns green.
Press ▼ key to display instrument parameters, as shown in figure 5.

Figure 5 Instrument Parameters

Figure 5 Instrument Parameters

Press ▼ key return to the main interface.

3.3 Main Menu
Pressstarting key on the main interface, and into menu interface, as shown in figure 6.

Figure 6 Main Menu

Figure 6 Main Menu

Setting: sets the alarm value of the instrument, Language.
Calibration: zero calibration and gas calibration of the instrument
Shutdown: equipment shutdown
Back: returns to the main screen
Press ▼or▲ to select function, pressstarting to perform an operation.

3.4 Settings
Settings Menu is shown in Figure 8.

Figure 7 Settings Menu

Figure 7 Settings Menu

Set Parameter: Alarm Settings
Language: Select system language
3.4.1Set Parameter
The settings parameter menu is shown in Figure 8. Press ▼ or ▲ to choose the alarm that you want to set, then pressstarting to execute operation.

Figure 8 Alarm level selections

Figure 8 Alarm level selections

For example, set a level 1 alarm as shown in figure 9, ▼ change the flicker bit, ▲value add 1. The alarm value set must be ≤ the factory value.

Figure 9 Alarm setting

Figure 9 Alarm setting

After setting, press starting to enter the setting interface of alarm value determination, as shown in Figure 10.

Figure 10 Determine the alarm value

Figure 10 Determine the alarm value

Pressstarting, success will be displayed at the bottom of the screen, and failure will be displayed if the alarm value is not within the allowed range.

3.4.2 Language
Language menu is shown in Figure 11.

You can choose Chinese or English. Press ▼ or ▲ to choose language, pressstarting  to confirm.

Figure 11 Language

Figure 11 Language

3.5 Equipment calibration
When the instrument is used for a period of time, the zero drift appears and the measured value is inaccurate, the instrument needs to be calibrated. Calibration requires standard gas, if there is no standard gas, gas calibration cannot be performed.
To enter this menu, need to enter the password as shown in figure 12, which is 1111

Figure 12 Password input interface

Figure 12 Password input interface

After completing the password input, press  startingenter to the device calibration selection interface, as shown in Figure 13:

Select the action you want to take and press starting enter.

Figure 17Calibration completion screen

Figure 13 Correction type selections

Zero calibration
Enter the menu to perform zero calibration in clean air or with 99.99% pure nitrogen. The prompt for determination of zero calibration is shown in Figure 14 .Confirm according to ▲.

Figure 14 Confirm the reset prompt

Figure 14 Confirm the reset prompt

Success will appear at the bottom of the screen. If the concentration is too high, the zero correction operation will fail.

Gas calibration

This operation is performed by connecting the standard gas connection flowmeter through a hose to the detected mouth of the instrument. Enter the gas calibration interface as shown in Figure 15, input the standard gas concentration.

Figure 15 Set the standard gas concentration

Figure 15 Set the standard gas concentration

The concentration of the input standard gas must be ≤ the range. Press  starting to enter the calibration waiting interface as shown in Figure 16 and enter the standard gas.

Figure 16 Calibration waiting interface

Figure 16 Calibration waiting interface

Automatic calibration will be executed after 1 minute, and the successful calibration display interface is shown in Figure 17.

Figure 17 Calibration success

Figure 17 Calibration success

If the current concentration is too different from the standard gas concentration, calibration failure will be shown, as shown in Figure 18.

Figure 18 Calibration failure

Figure 18 Calibration failure

4.1Notes
1)When charging, please keep the instrument shutdown to save charging time. In addition, if switch on and charging, the sensor might be affected by the difference of charger (or the difference of charging environment), and in serious cases, the value might be inaccurate or even alarm.
2)It needs 3-5 hours for charging when the detector is auto-power off.
3)After get full charged, for combustible gas, it can work 12hours continuously (Except for alarm)
4)Avoid using the detector in a corrosive environment.
5)Avoid contacting with water.
6)Charge the battery every one to two-three months to protect its normal life if it is not used for a long time.
7)Please be sure to start the machine in normal environment. After starting, take it to the place where the gas is to be detected after the initialization completed.
4.2Common Problems and Solutions
Common Problems and Solutions as table 4.
Table 4 Common Problems and Solutions

Failure phenomenon

Cause of the malfunction

Treatment

Unbootable

low battery

Please charge in time

System halted

Press thestarting button for 8s and restart the device

Circuit fault

Please contact your dealer or manufacturer for repair

No response on the detection of gas

Circuit fault

Please contact your dealer or manufacturer for repair

Display inaccuracy

Sensors expired

Please contact your dealer or manufacturer for repair to change the sensor

Longtime no calibration

Please calibrate timely

Calibration failure

Excessive sensor drift

Calibrate or replace the sensor in time

Product detail pictures:

Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng detail pictures

Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng detail pictures

Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng detail pictures

Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng detail pictures

Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng detail pictures

Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng detail pictures

Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng detail pictures

Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng detail pictures

Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng detail pictures


Related Product Guide:

"Quality 1st, Honesty as base, Sincere company and mutual profit" is our idea, in an effort to create consistently and pursue the excellence for Chinese Professional Portable Flammable Gas Concentration Meter Alarm - Portable combustible gas leak detector Operating instructions – Huacheng , The product will supply to all over the world, such as: Mauritania, Sao Paulo, Angola, If you have any requests, pls email Us with your detailed demands, we will give you the most wholesale Competitive Price with the Super Quality and the Unbeatable First-class Service ! We can give you the most competitive prices and high quality, because we are much more PROFESSIONAL! So please do not hesitate to contact us.
  • Product quality is good, quality assurance system is complete, every link can inquire and solve the problem timely!
    5 Stars By Gustave from Ghana - 2017.03.08 14:45
    Problems can be quickly and effectively resolved, it is worth to be trust and working together.
    5 Stars By Mike from kazan - 2017.09.26 12:12
    Write your message here and send it to us

    Related products

    • Manufacturing Companies for Temperature And Humidity Meter - Microcomputer automatic calorimeter – Huacheng

      Manufacturing Companies for Temperature And Hum...

      Microcomputer automatic calorimeter is suitable for electric power, coal, metallurgy, petrochemical, environmental protection, cement, papermaking, ground can, scientific research institutions and other industrial sectors to measure the calorific value of coal, coke and petroleum and other combustible materials. In line with GB/T213-2008 “Coal thermal determination Method” GB/T384 “Determination of calorific value of petroleum products” JC/T1005-2006 “Cement blac...

    • Bottom price Total Nitrogen Reagent - Laboratory products support custom laboratory various instruments and equipment – Huacheng

      Bottom price Total Nitrogen Reagent - Laborato...

    • New Arrival China Photovoltaic Weather Station - Miniature Ultrasonic Integrated Sensor – Huacheng

      New Arrival China Photovoltaic Weather Station ...

      Top appearance  Frontal appearance     Supply voltage DC12V ±1V Signal output RS485 Protocol Standard MODBUS protocol, baud rate 9600 Power consumption 0.6W Working  temperature -40-80℃ Working humidity 0-100%RH Standard cable length 2.5m Protection class IP65 Wind speed     Measuring range 0-40m/s Measurement accuracy ±0.5+2%FS Resolution 0.01m/s Wind direction     Measuring range 0-359° Measurement acc...

    • 2022 wholesale price  Centrifuge Tube Rack - Microcomputer automatic calorimeter – Huacheng

      2022 wholesale price Centrifuge Tube Rack - M...

      Microcomputer automatic calorimeter is suitable for electric power, coal, metallurgy, petrochemical, environmental protection, cement, papermaking, ground can, scientific research institutions and other industrial sectors to measure the calorific value of coal, coke and petroleum and other combustible materials. In line with GB/T213-2008 “Coal thermal determination Method” GB/T384 “Determination of calorific value of petroleum products” JC/T1005-2006 “Cement blac...

    • Hot Sale for Micro Pipette - Laboratory products support custom laboratory various instruments and equipment – Huacheng

      Hot Sale for Micro Pipette - Laboratory produc...

    • OEM Supply Remote Rain Gauge - Microcomputer automatic calorimeter – Huacheng

      OEM Supply Remote Rain Gauge - Microcomputer a...

      Microcomputer automatic calorimeter is suitable for electric power, coal, metallurgy, petrochemical, environmental protection, cement, papermaking, ground can, scientific research institutions and other industrial sectors to measure the calorific value of coal, coke and petroleum and other combustible materials. In line with GB/T213-2008 “Coal thermal determination Method” GB/T384 “Determination of calorific value of petroleum products” JC/T1005-2006 “Cement blac...